MEWOI-JYZ-HW Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault

MEWOI-JYZ-HW Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault

  • Main Features:: Permanent Fault: Transient Fault: Earth Fault,Low battery warning, lithium battery backup
  • Model No.:: MEWOI-JYZ-HW
Contact Us for QuotationEmail:mewoi@mewoi.comWhatsapp: +8618620373879

MEWOI-JYZ-HW  Overhead live line fault indicator, fault passage indicator(FPI),Permanent Fault,Transient Fault,Earth Fault

Introduction


         MEWOI-JYZ-HW Overhead Line Fault Indicator is usually used in 5~38KV (can be customized by 44KV, 69KV and 110KV ) overhead line power distribution network to monitor and detect short-circuit and earth fault. The fault signal is indicated by three ultra-bright blinking LEDs with 360º sight.

         The indicator can be mounted under live conditions with the help of an adapter and a hot stick. The parameters such as trip current, reset time,blinking interval, etc., can be read and adjusted by a bidirectional wireless tool. Permanent fault, transient fault and battery low voltage alarm can be distinguished and indicated separately by 3 different ultra-bright blinking LEDs. And the earth-fault can be indicated by two alternating different ultra-bright blinking LEDs.

Main Features

Permanent Fault:  Red ultra-bright blinking LED.

Transient Fault:  Green ultra-bright blinkingLED.

Earth-fault: Red and Green ultra-bright LEDs blinking alternately.

Low Battery Warning: Yellow ultra-bright blinking LED

Parameter Adjust: The parameters can be read and adjusted by bidirectional wireless tool.

Power Supply: The indicator can take power from overhead lines, with lithium battery as backup.

Technical Specification

Short-circuit Trip Current

(Phase to Phase

50~1200A adjustable, 1A step, 150A default
Trip Current Delay40, 80, 120, 200ms, can be set during production
Indication Unit Reset

1. Manual by magnet.         2. Time reset:adjustable,1second step,24h default,max.48h 

3. Auto delay reset after repower,1 second step,30s default max 5min,only for 

permanent fault

Protection Class & IK ClassIP68
Internal Type TestIEEE495-2007
Operation Temperature Range-40~+70℃
Power SupplyLithium battery type AA 3.6V/9Ah, replaceable
Battery Life10 years
Weight600g
DimensionsDiameter: 93mm  Height: 170mm
Accuracy Read&Set Parameter from Indicator

0A~300A ±3A,300A~800A ±1%

&433MHz in indicators to read and set parameter 

Cable Diameter Ranges6mm~42mm
Blinking Frequency10 per minute, adjustable
Max. load/fault Current1200A

System Frequency (Hz)Self-adjusting

50/60 Hz & 60s self-adjusting
Current withstand31.5KA/4s