MEWOI-T1200 Six phase relay protection test set, 6phase relay protection tester

MEWOI-T1200 Six phase relay protection test set, 6phase relay protection tester


Contact Us for QuotationEmail:mewoi@mewoi.comWhatsapp: +8618620373879

MAIN FEATURES


1,Meet all test requirements on site.The instrument has standard six phase voltage and six phase current output. It can test not only traditional relays and protection devices,   but   also   modern   micro-computer   protection   devices,   especially   for transformer differential protection and standby automatic switching device. The test

is more convenient and perfect.

2,All kinds of technical indexes fully meet the standard of DL / t624-1997 "technical conditions for microcomputer based test device of relay protection" issued by the

Ministry of electric power.

3,Classic Windows XP operation interface, friendly man-machine interface, easy and fast operation; high performance embedded industrial control computer and 10.4 inch  resolution  800   ×  600  TFT  true  color  display  screen,  can  provide  rich  and intuitive  information,  including  the  current  working  state  of  the  equipment  and

various help information.

4,This Windows XP  system  has  its  own  recovery  function  to  avoid  system  crash caused by illegal shutdown or misoperation.
5,Equipped with ultra-thin industrial keyboard and photoelectric mouse, it can complete all kinds of operations through keyboard or mouse just like ordinary PC.
6,The main control board adopts DSP + FPGA structure and 16 bit DAC output. It can generate 2000 high density sine wave per week for fundamental wave, which

greatly improves the quality of waveform and the accuracy of the tester.

7,The high fidelity linear power amplifier ensures the accuracy of small current and the stability of large current.
8,USB interface is used to communicate with PC directly without any connecting line,so it is convenient to use.
9,can be connected to laptop (optional) to run.Laptops and industrial computers use the same set of software, so there is no need to relearn the operation method.
10,It has the function of GPS synchronization test.The device can be built-in GPS synchronous card (optional) and connected with PC through RS232 port to realize

synchronous test of two testers in different places.

11,Equipped with independent dedicated DC auxiliary voltage source output, the output voltage is 110V (1a), 220V (0.6A).It can be used for relays or protection

devices that need DC power supply.

12,It has the function of software self calibration, which avoids opening the case to   calibrate the accuracy by adjusting the potentiometer, thus greatly improving the

stability of accuracy.

TECHNICAL PARAMETERS

1.AC current source (6 * 30a)

Single phase current output (RMS)

0 -- 30A / phase, accuracy: 0.2%  ±  5mA

six phase parallel output (RMS

0 – 180A / 6 same phase parallel output

Allowable  working  value  of  phase current  for  a  long  time   (effective value)

10A
Maximum output power per phase
300VA
Maximum output power of six phaseparallel current
1000VA

Six and the maximum output current allowed working time

5s
frequency range
0 -- 1000Hz, accuracy 0.001Hz
Harmonic number
2--20second
phase
0--360The accuracy is 0.1 degree

2. DC current source

DC current output

0-- ±  10A / phase, accuracy: 0.5%  ±  5mA

3. AC voltage source

Single phase voltage output (RMS)
0 -- 125V / phase, accuracy: 0.2%  ± 5mv
Line voltage output (RMS)
0--250V
Phase   voltage   /   line   voltage output power
75VA/100VA
Frequency range
0 -- 1000Hz, accuracy: 0.001Hz
Harmonic number
2--20second

phase

0--360Degree, accuracy: 0.1 degree

4. DC voltage source


Single    phase    voltage output amplitude

0-- ±  150V, accuracy: 0.2%  ±  5mv

Output amplitude of line voltage0-- ±300V

Phase   voltage/ line  voltage output power

90VA/180VA

5. switching value terminal

Switch input terminal
8yes
Air contact
1 -- 20 mA, 24 V, internal active output of thedevice
Potential reversal

Passive   contact:   low   resistance   short   circuit signal Active contact: 0-250V DC

Switch output terminal

4Yes, no contact, breaking capacity: 110V / 2a, 220V / 1a

6. others

time frame
1ms -- 9999s, measuring accuracy: 1ms

Volume and weight of single machine

Volume 410x190 x420mm3, about 18kg
Power Supply
AC220V±10%, 50Hz, 10A


Telephone
E-mail
After Sales
QQ