MEWOI-LX5265 Built-in battery/Printer TTR Tester 3-phase transformer turn ratio tester,transformer turn ratio finder,MEDIDOR DE RELAÇÃO DE TRANSFORMAÇÃO
Click to download: MEWOI-LX5265 3-Phase Transformer turn ratio tester User Manual
INTRODUCTION
The Preventive Test Rules of the State Ministry of Electricity require that the transformer be tested periodically for turn-to-turn ratio or voltage ratio, including semi-finished products and finished products in the production process, transformers before putting in o operation and during the operation of the power system. The traditional variable-ratio bridge is complicated to operate and its reading is not intuitive. It needs necessary conversion, and the test results only reflect one-phase ratio. MEWOI-LX5265 Transformer Turn Ratio Tester overcomes the shortcomings of the traditional bridge test, completes the three-phase ratio test at one time, has fast test speed and high accuracy, and greatly improves the test efficiency. |
MAIN FEATURES
1, Lithium battery power supply or 100-240V AC power supply is self-adaptive. After one charge, more than 100 transformers can be continuously tested in the ratio group. The test process is simple and convenient. |
2, It has the function of blind measurement, that is, to perform variable ratio and group test when there is no connection between high and low voltage. |
3,Based on the test of conventional transformer, Z-type transformer and PT sample, the polarity test function of CT variable ratio is added, and the application field is wider |
4, Wide range and high accuracy, the variable ratio measurement range can reach 10,000, and the test accuracy can be guaranteed 0.3% when the maximum value is 10,000. |
5, It has perfect protection functions such as reverse connection protection and output short circuit protection. |
6,5.6-inch super industrial high-brightness color LCD screen, still visible under strong sunlight. |
7, equipped with external printer, facilitate data printing |
8, It can be stored locally and on USB memory. |
TECHNICAL SPECIFICATION
Measure Range | 0.9~10000 |
Accuracy
| 0.1%±2dgt(below 500); 0.2%±2dgt(500~3000); 0.3%±2dgt(>3000); |
Resolution | 0.9~9.9999(0.0001),10~99.999(0.001),100~999.99(0.01),1000~9999.9(0.1),10000 and above(1) |
Output voltage | 160v/10v (automatic selection). |
Working power | The built-in battery or external charger, charger conditions of use,Input 100-240 VAC,50/60 HZ |
Charging Time | About 2 hr |
Weight | 1.7KG |
Dimension | 246 mm(L)×156 mm(W)×62 mm(H) |
Working Temperature | –10°C ~ 50°C. |
Relative Humidity | ≤90%, no condensation |
Accessories |
1 Hand-held transformer turn ratio tester 1 sets of test lines (red and black each) 1 charger(optional) 1 external printer (with printing cable attached) 1 wrist band (attached to a hand-held tester)) 1 print user manual 1 copy of certificate and factory test report |
SELECTION GUIDE
Model No. | Range | Accuracy | Resolution | Output voltage | Working Power | RS232/USB | Printer |
MEWOI-LX5265 | 0.9~10000 | 0.1%±2dgt(below 500); 0.2%±2dgt(500~3000); 0.3%±2dgt(>3000); | Minimum 0.0001. | 160v/10v (automatic selection). | AC220v ± 10%, 50hz Built-in battery | USB/RS232 | External Printer |
MEWOI-UCT-B | 0.9~10000 | 0.1%±2dgt(below 500); 0.2%±2dgt(500~2000); 0.3%±2dgt(2000~4000); 0.5% ± 2dgt(4000 or more). | Minimum 0.0001. | 160v/10v (automatic selection). | AC220v ± 10%, 50hz. | - | √ |
MEWOI-UCT-C | 0.9~10000 | 0.1%±2dgt(below 500); 0.2%±2dgt(500~2000); 0.3%±2dgt(2000~4000); 0.5% ± 2dgt(4000 or more). | Minimum 0.0001. | 160v/10v (automatic selection). | AC220v ± 10%, 50hz Built-in battery | -
| √ |
MEWOI-YH128A | 0.9~5000 | 0.1%±2dgt(below 500); 0.2%±dgt(500~2000); 0.5%±2dgt(2000~5000); | Minimum 0.0001. | 160v/10v (automatic selection). | AC220v ± 10%, 50hz. | √ | √ |
MEWOI-YH128B | 0.9~10000 | 0.1%±2dgt(below 500); 0.2%±2dgt(500~2000); 0.5%±2dgt(2000~10000); | Minimum 0.0001. | 160v/10v (automatic selection). | AC220v ± 10%, 50hz. | √ | √ |