• MEWOI-DRS5(DC)-1000mA Leakage Current Sensor

MEWOI-DRS5(DC)-1000mA Leakage Current Sensor

  • Name:
    MEWOI-DRS5(DC)-1000mA Leakage Current Sensor
  • Model No.:
    MEWOI-DRS5(DC)-1000mA
  • Main Features:
    small DC Leakage Current Measurement
Electricity Testing Instruments manufacturer, Support OEM/ODM, your testing specialist
share:

TECHNICIAL SPECIFICATION

Click to download:MEWOI-DRS5(DC) Specification

Model NumberMEWOI-DRS5
Diameter
φ20mm
Rated input Current (IPN)10
20501002005001000mA(AC)
Primary Current Measure range(IP)0~±200~±300~±700~±1200~±2200~±6000±1200mA
Rated output voltage of secondary side5(DC)or5(AC) (±1%)V
Power Supply Voltage (VCC)±12V or+24V (5%)V
Current consumptionVCC = ±12V                      <20mA
Galvanic isolation (Vd)2.5KV /50Hz/1min
Linearity (εL)<1%FS
Offset Voltage V0TA =25℃                  <±25mV
Offset Voltage drift VOTIP=0  TA =-10~+60℃              <±1.5mV/℃
Operating temperature TA-25~+70
Storage temperature TS-40~+85
Load resistance RL≥10KΩ


blob.png

Matters needing attention

1, The wrong connection may cause sensor damage. After the sensor is energized, the same phase voltage is measured at the output when the current wire cross the sensor center according the direction arrow indicating label.

2, The output range of the sensor can be adjusted according to the user's needs.

Selection Guide

Model NumberRangeDiameterOutputPower Supply

MEWOI-DRS4A.80.jpg

MEWOI-DRS4A

1000mA20mm5(DC)or5(AC) (±1%)±12V or+24V (5%)

MEWOI DSR5.80.jpg

MEWOI-DRS5

1000mA20mm5(DC)or5(AC) (±1%)±12V or+24V (5%)

MEWOI-DRSL.80.jpg

MEWOI-DRSL2000

2000mA33mmDC ±5V, 4-20mA, 0-20mA (±1%)DC ±12V~±15V  (±5%)

MEWOI-DRSL.80.jpg

MEWOI-DRSL100

100mA33mmDC±5V(±1%)DC±12V (±5%)

MEWOI-DRST(DC)-200mA_80.jpg

MEWOI DRST

2000mA19mmDC ±5V, 4-20mA, 0-20mA (±1%)DC ±12V~±15V  (±5%)

TAG:   Leakage current sensor leakage current transformer